ELECTRICAL TECHNOLOGY AND INDUSTRIAL PRACTICE

It's An Ani's effort..


It is all about Electrical Technology and its industrial practices....


RECENT POSTS




Wednesday, September 30, 2020

September 30, 2020

Energy-Definition, Unit of energy, Relationship between different unit of energy

 Details of energy, definition of energy,  unit of energy, relationship between them

Definition of energy: 

The ability or capability of a body for doing a work is known as energy. There are several kind of form of energy, but the most important ones are - 1. electrical energy, 2. mechanical energy and 3. thermal energy.

Now remember these energies are all interchangible.

Unit of energy:

Energy is a measurable quantity so we need to assign unit to energies, and as the energies are interchangeable so their unit should also have relation between them or same unit can be assigned because the energies are just in different forms.

1. Electrical Energy: The SI unit of electrical energy is watt-second also known as joule. Suppose there are two points which have a potential difference of 1 volt now a current of 1 ampere is flowing from one point to another. 

So Power is equal to 1 volt * 1 ampere =1 watt. 

Now if this continues for 1 second, then the energy consumed will be 1 watt * 1 second that is equal to 1 watt-second. 

In case the system is AC then another factor called power factor comes into picture, 

so, watt-second =1 volt * 1 ampere * power factor *1 second.

2. Mechanical Energy:

Unit of mechanical energy in SI system is Newton metre also known as joule. When a force of 1 Newton makes a body move by 1 metre distance then the work done on the body is 1 joule or 1 Newton metre.

3. Heat Energy:

Unit of heat energy in SI unit is joule. There are also other units that is calorie, British thermal unit or B. Th. U etc. Calories stands for the amount of heat energy that is required to increase the temperature of 1 gram water by 1 degree centigrade.

similarly British thermal unit can be expressed as the heat energy required to increase the temperature of one pound water by one degree fahrenheit.

Relationship between the unit of energy

All the three energies as mentioned above is convertible from one form to another, so their units are also have a relationship between them, and another thing is there to remember that all the three energies can do some work so they should have a common unit, and we can see that all the three energies have a common unit that is "Joule" now let us see the relationship between them.

Relationship between kWhr and Joule

1 kWhr (Unit)

= 1000 watt * 1 hr

=1*10^3 watt*3.6*10^3 sec.

=3.6*10^6 watt- sec= 3.6*10^6 Joule


Relationship between kWhr and N-m

1 N-m = 1 Joule

1 kWhr= 3.6*10^6 Joule

= 3.6*10^6 N-m

Relationship between Calorie and kWhr

1 kWhr=3.6*10^6 Joule

Again,

1 Calorie=4.18 Joule (Experimental value)

So, 

1 Joule= 1/4.18 Cal

So,

1 kWhr= 3.6*10^6/4.18 Cal


Monday, September 7, 2020

September 07, 2020

Basic of Electrical Energy|Electrical Energy Fundamentals

Basic of Electrical Energy


Basic of electrical energy|Electrical Energy Fundamentals

Energy means everything. Just imagine yourself with lots of energy. How many thing you can do. Similarly if you are without energy you won't be able to do anything. The backbone of development is energy. Our modern world is building continuously with the help of energy.


There are many variants of energy such as kinetic energy, static energy, thermal energy, e mechanical energy etc. But the most useful one is the electrical energy. Also as electrical Engineer we will focus on electrical energy. However please remember all energies are convertible from one form to another.

What are the major advantages of electrical energy?


Why electrical energy is so important?

We need energy in different forms some time for cooling, some time for heating, as light, as motion. Now I just rewind your basic and you can find that electrical energy can be converted to all of them. This is the main advantage of electrical energy. So let us list down the advantages of electrical energy.

1. Environment-friendly: Electrical energy clean and environment friendly. Pollutes the atmosphere very less. It does not produce toxic gases.

2.Ease of transmission distribution and control: You can transfer electrical energy over several thousand kilometres with the help of conductor. You can distribute it as you want also you can control the energy by only switching on or off a circuit.

3. Easily convertible: Electrical energy can be converted to rotational energy (motor), photoenergy (light), heat energy (heater or air conditioner), sound energy (speaker) etc. with ease. No other form of energy is such easily convertible.


Source of electrical energy!!!! No no we should say conversion of other energy into electrical energy.

We know that energy cannot be created or destroyed. It can only transform from one form to another.

So there are many kind of preliminary source of energies from where electrical energy can be obtained.

The major sources and form of energies are

1. Fuel (solid/liquid/gas): Solid or coal, liquid or oil, or fuel gas have calorific values which releases heat when burnt. Now this heat is used to convert water into steam. This steam is thrown on steam turbine, so heat energy is converted to kinetic energy. The steam turbine is coupled with alternator. The alternator when rotates generates electrical energy. Liquid fuel is used in internal combustion engine which rotates and generator connected with it generate electrical energy. Gas is often used in gas turbine which generates electrical energy as generator connected with it.

2. Water: Water when stored at high level or its flow is restricted by dam, it stored static energy. So if it is released through a pipe the energy is released as kinetic energy. Now this water is fall on water turbine. The Kinetic linear energy is then converted into rotational energy. So the water turbine rotates and as alternator is coupled with the turbine so the alternator also starts rotating and generates electrical energy.

3. The Sun: The Sun gives us heat energy and photo or light energy. Both can be converted to electrical energy. From light energy emitted by sun, electrical energy can be obtained by using solar photovoltaic cell commonly known as solar panel, which converts light energy to electrical energy. Also the heat energy is collected via reflector and used to heat up the water which eventually converts into steam and operates the steam turbo generator.

4. Wind: At coastal area wind has high kinetic energy so the wind turbines are installed at coastal areas. With these wind turbine often known as wind mill a generator is coupled inside it. So when wind blows the turbine it starts rotating and the generator located inside also starts rotating and it generates electricity.

4. Nuclear: Nuclear energy is another kind of source from where we can extract electrical energy. There are sevaral radioactive material which participate in fission reaction and generates heat. This heat, coming out of the nuclear energy can converts water into steam. This steam is thrown to the turbine, the turbine rotates, and the alternator coupled with the turbine also rotates. So electricity is generated.

5. Chemical energy: Inside battery due to chemical reaction energy is generated.

These are the major source of energy. Apart from the above geo thermal energy, tidal energy etc. are also used for electrical energy generation.


Hope you have enjoyed this article.

Thank you very much....



Saturday, September 5, 2020

September 05, 2020

Momentary Paralleling of transformers or sources|Part 1|Operation sequence of momentary Paralleling|How momentary Paralleling is implemented

What is Momentary Paralleling of Transformer or incomers? Momentary Paralleling


In books you will mostly find parallel operation of transformers. In practice you will find its momentary operation. That is momentary Paralleling. Now there will come several questions.

1. What is momentary Paralleling?

2. Why we use momentary Paralleling?

3. Why continuous Paralleling of Transformer isn't used for distribution level?

Now let us answer one by one.

We all know that parallel operation of transformers means when two or more nos. of transformers are connected together in a same bus bar.

Main advantage of Paralleling is that addition of transformer can take up additional loads. But it has a major disadvantage. The main disadvantage of continuous parallel operation is that the fault level becomes double. So for distribution level parallel operation is hardly used. 

Suppose you need to deliver say 2 MVA power. Now if you select 2 nos of 1.25 MVA transformers with 6% percentage impedance and run them in parallel so their equivalent percentage impedance will be 6/2=3%. So total fault MVA will be 1.25/0.03=41.67 MVA

But if we select 2.5 MVA trafo with 9% impedance then our fault MVA will be 2.5/0.09=27.77 MVA.

Now one may say what if we consider 12% percentage impedance for 1.25 MVA trafo, but that is not feasible as that will cause huge voltage drop.

Moreover if one transformer fails you will loose 50% of source.

So it is often practiced to use the source with additional 100% capacity so that redundancy is maintained

Now you have understood why Paralleling is not used in distribution level.

Now comes the Momentary Paralleling. Momentary Paralleling is two transformers or two sources connected in parallel for a short duration, then either one of the source is disconnected or the Paralleling is discontinued.

Momentary paralleling of two sources
Momentary paralleling of two sources
https://electricaltechnologyrishi.blogspot.com


Suppose in the above picture there are two incomers. But one is in circuit or switched on and the other is off. Now you need to maintain source 1, so you want to off source 1 and want to feed the loads from source 2. If you switch off source 1 breaker, and then close source 2 breaker then all the loads will be shut down. And you will need to restart the entire system. So to avoid this interruption we will go for momentary Paralleling. So for a brief period of time both thr sources will connected i.e. paralleled. After a pre set time one source (Source 1) be tripped. So you need a trip selector switch or TSS to select which source will be tripped. But if the selected source fails to trip the incoming source (here source 2) will trip to avoid sustain Paralleling.

Now let us see another case where the system bus has two sources from two transformers and they are isolated by a bus coupler.

Momentary paralleling with two incomer and one bus coupler
Momentary paralleling of two sources with bus coupler
https://electricaltechnologyrishi.blogspot.com


Normal operating condition is both the incomers i.e. incomer 1 and incomer 2 is closed and delivering loads, and the bus coupler is open, so that there is no paralleling between the two sources. So here bus coupler is Paralleling components.

Case-1

Now as we mentioned that we select transformer with 100% backup so we can switch off one source. Suppose we want to take transformer 2 in maintanence, so we need to open the incomer 2 breaker, and for feeding loads of that bus section we need to close the buscoupler. Now we will do it by momentary Paralleling so that loads are not interrupted.

So our target is closing of bus coupler and

Opening of incomer 2 breaker. 

Remember that momentary Paralleling is a manual process, so we need to put the selection at manual mode. Only that will allow closure of all three breakers after synchro checking. Otherwise these three breakers will be interlocked, so you will be able to close only two breaker at a time.

Hence, Trip Selector switch i.e. TSS shall be at Incomer 2 position, i.e. incomer 2 will trip.

Now we will give close command to buscoupler. Synchro check relay will check the incoming source voltage details with the running system voltage details i.e. magnitude, phase sequence, frequency etc.

Incoming power source is determined by the trip Selector switch position.

After the synchro check relay compares the two circuits the bus coupler get closed if permissive is given by synchro check relay.

So now all the three sources are closed. And a timer get energized. After certain time incomer 2 will open and deactivate the timer.

Now here is an interesting thing, if the incomer 2 doesn't trip, the timer will remain energized, and then it will send trip signal to bus coupler so that sustain Paralleling doesn't occurs.

Case 2:

In case 1 we have seen that we have taken transformer 2 out of service for maintenance with closing the buscoupler, and shifting the loads to transformer 1 by momentary Paralleling. So suppose our transformer 2 is inspected and ready to be in operation, so we want to back in our normal operation i.e. two incomers are running and bus coupler is open. So here also we will do the same thing with momentary Paralleling.

Now our trip Selector switch or TSS will be at bus coupler, because we want to trip the bus coupler after successful momentary Paralleling.

And auto-manual selection shall be at manual mode operation. Often this is given as Auto-Independent-Manual selector switch.

Now we will give close command to incomer 2. Synchro check will be between bus Pt at bus B and line PT for incomer 2. If there is no variation or variations are with in tolerable limit incomer 2 will get closed, and after some time bus coupler will open.

Case 3

Scenario may me something else. Our switchboard incomers and bus coupler often has auto change over scheme. Suppose two incomers ar closed and bus coupler is opened. Now there is a problem at transformer 2, so incomer 2 will trip due to under voltage. Due to the auto change over scheme bus coupler will automatically close after incomer is tripped (only condition is lock out relay of incomer 2 has not operated i.e. no fault at incomer 2). 

Now we have cleared the fault and want to bring back incomer 2 into circuit, with out interruption of the power supply to the loads. So we will use momentary Paralleling. Our Trip Selector switch shall be at bus coupler, and incomer 2 shall be closed. Bus coupler will automatically open.

So this how momentary Paralleling works and applied. 

Hope you have enjoyed the article. In the second part of the article we will be discussing about the control schematic of momentary Paralleling.


Thank you......

Saturday, August 29, 2020

August 29, 2020

CT burden calculation| How to calculate burden of Current Transformer

CT burden calculation. How to calculate Current Transformer burden






Before starting the discussion about CT or current transformer burden calculation we should know what is a burden!!!!!!

Burden is something which irritates?!!!! Actually burden is some additional load, which you need to bear.

Just like that the current transformer also need to drive some load which is called burden of CT or current transformer. Now what are the burdens?

For knowing that we need to understand what are the elements that are connected with the current Transformer. A protection class CT or current transformer has relays connected with it. And a metering class CT has mainly ammeter and multifunction meter connected with it. All this instruments has a small amount of power demand which is imposed on the current Transformer as burden of CT.

So basically sum of power demand of the instruments connected with the CT is called burden of CT. 

Now for outdoor switchyard what happened the current Transformer is installed on field. But the relay, MFM, ammeter etc are installed a certain distance away from the CT location, inside a panel. And this distance is connected via cable. So now there is a power loss in the cable, so that loss will also be included in CT burden calculation.

This is called lead burden. However lead burden js applicable mostly for CT installed at out door. Now,

Circuit diagram for Meter and relay connected with CT
Single line diagram of metering and protection
https://electricaltechnologyrishi.blogspot.com

Let us consider this picture. Here we can see a an Ammeter, a Tri vector meter and an MFM is connected in series with the current Transformer. So their VA rating will be added to the burden of CT.

Now from a typical catalogue of MFM and ammeter we have found that

Ammeter has a burden of around 0.9 VA.

MFM has burden of 0.5 VA (MFM  has two burden, one is on CT and the other one is on PT)

And TVM has a burden of say 0.6 VA.

So their total VA demand=2 VA.

Now we will calculate the lead burden. It is assumed that CTs are outdoor type, and they are connected with the meters with cable. Now we will find out the power loss in the cable.

CT burden calculation
Three line diagram of metering connection to CT
https://electricaltechnologyrishi.blogspot.com


So from the above diagram we can see that each CT is connected to the meter. So for completing the operating circuit(i.e. you can see that as per the ammeter selector switch position two leads will be connected between CT and meters, so we need to consider two cable) two nos. of cable runs are required, so we need to calculate the power loss for two runs. Generally 2.5 sq. mm Cu cables are used for such connection, so we will also consider the same.

2.5 sq mm Cu cable has resistance of 9.8 Ohm/ km.

Let's say the metering panels and CTs are 100 m away so we need to calculate resistance of 200 m cable. 200 is considered for to and fro run.

So total resistance will be 9.8*200/1000=1.96 Ohm

Say CT secondary rating is 1A, so total power loss=I^2*R=1*1*1.96=1.96 VA.

So, total burden will be 2+1.96=3.96 VA

So CT selected VA should be minimum 5 VA, however considerable margins are kept to burden selection.

Say the burden is selected as 15 VA.

Now let us see the condition for protection CT.

Relay connection to CT
Relay connection to the current Transformer
https://electricaltechnologyrishi.blogspot.com

From the diagram we can see the connection of the Relay with the CT. Here also for calculating the lead burden our consideration will similar as that for protection.

Since the relay, meter all are housed in a same panel so lead resistance will be same for both the case.

Numerical relay has burden of around 0.2 VA. So total burden for protection CT is 1.96+0.2= 2.16 VA.

Let us select 15 VA CT. Now Selection of such higher value of CT burden will give us another advantage. We will see that.

Suppose our selected CT is 5P20 class CT, i.e. its Accuracy limit factor is 20. Now if the VA is higher the actual ALF will increase.

The corrected or actual accuracy limit factor or ALF can be found as following

ALF'=ALF*(Pi+Pn)/(Pi+Pr)

Where 

ALF'= The actual accuracy limit factor

ALF= Rated accuracy limit factor

Pi=CT internal I^2*R loss

Pn=Selected CT burden

Pr=Actual burden on CT.

Out CT is 1A secondary rated, and CT resistance shall be maximum 5 ohm (Rct<=5 ohm).

So, Pi=5VA

Pn= say 15

Pr= 2.16 VA (burden of numerical relay and cable)

And the CT is a 5P20 CT so ALF=20.

So, ALF'= 55.86

So our 5P20 CT will act like 5P56.

Its accuracy limit factor will increase. So thus the actual ALF of CT increases with higher burden selection.


Hope you have enjoyed this article. Please visit the sitemap for all articles.

Thank you......







Tuesday, August 18, 2020

August 18, 2020

Why AC is preferred over DC

 Why is Alternating current or AC is preferred over Direct Current or DC


In our early days the main power distribution used to be carried out by DC or direct current. The direct current distribution was developed by Thomas Edition. 

Later on one of his employee Nicolas Tesla developed alternating current or AC. Gradually AC or alternating current over took the direct current distribution or DC distribution. 

Now question arises that why direct current or DC usage got reduced and Alternating Current or AC gained popularity. There are many advantages of AC power over DC. 

In this article we will be discussing about those advantages.

The first reason of Alternating Current or AC having such application is

1. The induction phenomenon.

Due to this induction the Transformer is introduced which can easily change the voltage level. Changes voltage is very much essential for a successful Power system. Why??? Let's see......

We know that Power=Voltage×Current. Now if we want to transfer a huge amount of power and we don't increase the voltage, the current will increase. High value of current will cause high power loss, voltage drop, heating, heavy conductor cross section. Overall causing poor power system. Hence we need to increase the voltage for sending the power. Again at the receiving end we need to reduce back the voltage at our desired utilisation level. So frequent changes in voltage is desired for a healthy power system. Now this process becomes very easy with transformer and Alternating Current or AC.

But changing in voltage with DC is very difficult as it needs power electronics device.

So that is very important reason we are using AC over DC.

2. Circuit Breaking Ease.

Alternating Current or AC changes its magnitude with respect to time i.e. it starts from zero, goes to its maximum value, then come backs to zero, then goes to negetive magnitude (i.e. changing the direction of flow) and again goes to zero. So for completing a cycle an AC wave crosses three no zeros. At those point of the circuit has no voltage, and therefore no current or arc. So the insulation at the break point can be easily established at the point zero crossing, making the circuit breaker to operate with less difficulty.

Why ac is preferred over DC
AC signal with zero crossing
https://electricaltechnologyrishi.blogspot.com


But in direct current or DC breaker as DC has no zero crossing it is difficult to extinguish the arc, and re establish the insulation.

Whys is ac prefered over DC
DC signal with no zero crossing
https://electricaltechnologyrishi.blogspot.com


So for easy circuit Breaking and fault isolation AC is preferred over DC.

3. Low Cost of Metering instrument for AC than DC.

In AC system we have instrument transformer which reduces the voltage and current at lower level suitable for measurements. But in direct current or DC system there is no such Instrument transformer. So other type of sensors are required for measurements.

Also for AC measurement Moving Iron instruments are used which is less expensive that PMMC instrument that are used for DC.

To over come these difficulties in HVDC often the circuit Breaking and measurement is made at AC side.

So these are the three major reason for which AC power is preferred over DC power.

Apart from these there are also may factors like 

4. DC  equipment like motor, generators are bulky in size due to huge copper winding, competitively AC machines are robust in size.

5. DC machines are doubly excited machine where as AC machines are singly excited(induction motor)

6. No need to replace Carbon brushes as that required in DC machine.

7. Due to absense of Brushes there is no commutation problem in AC machines, no spark.


So these are the main reason why we shifted to Alternating Current system from direct current supply system.


Hope you have enjoyed this article.

Please visit the sitemap for all articles ........