ELECTRICAL TECHNOLOGY AND INDUSTRIAL PRACTICE

It's An Ani's effort..


It is all about Electrical Technology and its industrial practices....


RECENT POSTS




Sunday, August 26, 2018

August 26, 2018

Restricted Earth Fault Protection-CT SELECTION-PART 1 :RATIO SELECTION

SELECTION OF PROPER CURRENT TRANSFORMER IS ONE OF THE IMPORTANT PART OF A PERFECT PROTECTIVE SYSTEM. IF THE PROTECTION IS DONE BY DIFFERENTIAL THEN IT HAS THE MOST IMPORTANCE.....


Any protective system is basically a "Detection system" which detects any abnormality. CTs are the eyes of a relay. A relay monitors the system condition through the CT.

As mentioned in the article "Restricted Earth Fault Protection Philosophy REF  is basically a differential protection.

Needless to say that differential protection requires most sophisticated and accurate CTs, as very marginal error can cause mal-operation of the relay.

Saturday, August 18, 2018

August 18, 2018

Restricted Earth Fault Protection Philosophy

"WHAT IS RESTRICTED EARTH FAULT PROTECTION??". BUT MORE IMPORTANT THAN "WHAT" IS "WHY" RESTRICTED EARTH FAULT PROTECTION

The name suggest the principle. It is restricted. What does it mean and why we need such restriction. Lets go deeper.

It is restricted between a certain zone. That means the protection function will work only within a specified zone that is pre-determined.
Suppose you have selected a certain boundary, this restricted earth fault protection (REF) will detect earth fault only within that range. Earth fault out side the boundary will not be detected by the REF scheme.


Protection against earth fault is very much essential for the machine having a core such as generator, transformer & motors. The most occurred and severe earth fault happens when insulation of winding get damaged, and it touches the core of the machine. Since core is kept earthed, this situation causes an Earth fault.

Sunday, August 12, 2018

August 12, 2018

CT connection to sense earth fault/Earth Faults Detection Philosophy

CT CONNECTION FOR EARTH FAULT DETECTION


Earth fault relays like 51N/50N detects earth faults because of the CT connection. There are three major types of connections for 51N/50N.


i.Residually connected CTs.

ii.CBCT(core balance CT)/ZCT(Zero sequence CT) connection.

iii.CT connected in transformer neutral.